LHH Hibalon

LHH Hibalon

  • Applicable Fields and Scope: Generator, electric motor, transformer lead-out wire, or wiring in locations with higher temperature resistance.
  • Rated Voltage: 600V
  • Rated Temperature: 90°C
  • Conductor: Tinned Copper Soft Wire (T.C)
  • Insulation: Hibalon Rubber
  • Standards: Refer to CNS 5747, JIS C 3315.
  • Characteristics: Excellent flexibility, able to withstand impact, bending resistance, wear resistance, and tensile stress. It also possesses oil resistance, chemical resistance, heat resistance, and weather resistance.
PDF
Product Category Product Code Conductor Insulation Allowable Current (Approx.) in Amperes (A) Maximum Conductor Impedance in Ohms per Kilometer (Ω/km) Minimum Insulation Impedance in Megaohms per Kilometer (MΩ/km)
Cross-Sectional Area
mm²
Construction
No./mm
Diameter
mm
Thickness
mm
Outer Diameter
mm
45℃ 75℃
Hibalon
LHH00075 0.75 30/0.18 1.1 1.1 3.40 16 12 25.8 6
LHH00125 1.25 50/0.18 1.5 1.1 3.70 22 17 15.5 6
LHH00200 2 37/0.26 1.8 1.1 4.10 30 22 9.91 6
LHH00350 3.5 45/0.32 2.5 1.1 4.70 45 32 5.38 6
LHH00550 5.5 35/0.45 3.1 1.1 5.30 58 41 3.46 6
LHH00800 8 50/0.45 3.7 1.1 5.90 73 51 2.45 5
LHH01400 14 88/0.45 4.9 1.1 7.10 105 70 1.39 5
LHH02200 22 7/20/0.45 7.0 1.4 9.60 140 100 0.892 5
LHH03000 30 7/27/0.45 8.1 1.4 11.0 180 130 0.661 5
LHH03800 38 7/34/0.45 9.1 1.4 11.54 210 140 0.525 5
LHH05000 50 19/16/0.45 10.4 1.8 13.45 250 175 0.411 3
LHH06000 60 19/20/0.45 11.6 1.8 14.25 290 180 0.329 3
LHH08000 80 19/27/0.45 13.5 1.8 16.25 350 240 0.243 3
LHH10000 100 19/34/0.45 15.2 2.3 18.65 410 265 0.193 3
LHH12500 125 19/42/0.45 16.9 3.0 20.80 480 308 0.156 3
LHH15000 150 27/34/0.45 18.7 3.0 22.10 520 338 0.136 3
LHH20000 200 37/34/0.45 21.2 3.0 25.50 630 410 0.0933 3
LHH25000 250 37/42/0.45 23.6 3.0 27.80 720 478 0.0803 3
LHH32500 325 37/55/0.45 27.0 3.0 29.50 840 564 0.0614 3