600V 380℃ Heat-resistant Fire Alarm Cable
- The suitable applications and scope for the 600V 380℃ heat-resistant fire alarm cable include fire-fighting equipment, fire alarm systems, emergency power supply systems, broadcasting systems, and communication systems.
- Rated Voltage: 600V
- Rated Temperature: 380℃, withstand the heat test for 15 minutes.
- Conductor: Stranded copper wire
- Insulation: XLPE (Cross-linked polyethylene)
- Sheath: PVC (Polyvinyl chloride) or LSFH (Low Smoke and Fume Halogen-Free) as specified.
- Specification: Compliant with CNS11175 standard and approved by the Fire Department of the Ministry of the Interior for heat-resistant wires and cables.
Product Category | Product Code | Cross-sectional Area × Number of Cores mm × C or P | Conductor | Insulation Thickness | Jacket Thickness mm | Finished Outer Diameter mm | Maximum Conductor Impedance in Ohms per Kilometer (Ω/km) | Minimum Insulation Resistance MΩ-km | |
---|---|---|---|---|---|---|---|---|---|
Construction No./mm | Outer Diameter mm | ||||||||
600V 380℃ Heat-resistant Fire Alarm Cable (1.2mm) | |||||||||
HR000120D | 1.2 mm × 1C | 1/1.2 | 1.2 | 0.4 | 0.9 | 3.8 | 16.0 | 50 | |
HR12002 | 1.2 mm × 2C | 1/1.2 | 1.2 | 0.4 | 0.9 | 5.9 | 16.0 | 50 | |
HR12003 | 1.2 mm × 3C | 1/1.2 | 1.2 | 0.4 | 0.9 | 6.3 | 16.0 | 50 | |
HR12004 | 1.2 mm × 4C | 1/1.2 | 1.2 | 0.4 | 0.9 | 6.8 | 16.0 | 50 | |
HR12005 | 1.2 mm × 5C | 1/1.2 | 1.2 | 0.4 | 0.9 | 7.3 | 16.0 | 50 | |
HR12006 | 1.2 mm × 6C | 1/1.2 | 1.2 | 0.4 | 0.9 | 7.9 | 16.0 | 50 | |
HR12008 | 1.2 mm × 8C | 1/1.2 | 1.2 | 0.4 | 0.9 | 8.6 | 16.0 | 50 | |
HR12010 | 1.2 mm × 10C | 1/1.2 | 1.2 | 0.4 | 0.9 | 9.9 | 16.0 | 50 | |
HR12012 | 1.2 mm × 12C | 1/1.2 | 1.2 | 0.4 | 0.9 | 10.3 | 16.0 | 50 | |
HR12016 | 1.2 mm × 16C | 1/1.2 | 1.2 | 0.4 | 0.9 | 11.3 | 16.0 | 50 | |
HR12020 | 1.2 mm × 20C | 1/1.2 | 1.2 | 0.4 | 0.9 | 12.6 | 16.0 | 50 | |
HR12024 | 1.2 mm × 24C | 1/1.2 | 1.2 | 0.4 | 0.9 | 13.9 | 16.0 | 50 | |
HR12030 | 1.2 mm × 30C | 1/1.2 | 1.2 | 0.4 | 0.9 | 14.8 | 16.0 | 50 | |
HR12002P | 1.2 mm × 2P | 1/1.2 | 1.2 | 0.4 | 0.9 | 8.6 | 16.0 | 50 | |
HR12003P | 1.2 mm × 3P | 1/1.2 | 1.2 | 0.4 | 0.9 | 9.5 | 16.0 | 50 | |
HR12004P | 1.2 mm × 4P | 1/1.2 | 1.2 | 0.4 | 0.9 | 10.5 | 16.0 | 50 | |
HR12005P | 1.2 mm × 5P | 1/1.2 | 1.2 | 0.4 | 0.9 | 11.4 | 16.0 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (1.6mm) | |||||||||
HR000160D | 1.6 mm × 1C | 1/1.6 | 1.6 | 0.45 | 0.9 | 4.3 | 9.01 | 50 | |
HR16002 | 1.6 mm × 2C | 1/1.6 | 1.6 | 0.45 | 0.9 | 6.9 | 9.01 | 50 | |
HR16003 | 1.6 mm × 3C | 1/1.6 | 1.6 | 0.45 | 0.9 | 7.3 | 9.01 | 50 | |
HR16004 | 1.6 mm × 4C | 1/1.6 | 1.6 | 0.45 | 0.9 | 8.0 | 9.01 | 50 | |
HR16005 | 1.6 mm × 5C | 1/1.6 | 1.6 | 0.45 | 0.9 | 8.7 | 9.01 | 50 | |
HR16006 | 1.6 mm × 6C | 1/1.6 | 1.6 | 0.45 | 0.9 | 9.4 | 9.01 | 50 | |
HR16008 | 1.6 mm × 8C | 1/1.6 | 1.6 | 0.45 | 0.9 | 10.2 | 9.01 | 50 | |
HR16010 | 1.6 mm × 10C | 1/1.6 | 1.6 | 0.45 | 0.9 | 11.9 | 9.01 | 50 | |
HR16012 | 1.6 mm × 12C | 1/1.6 | 1.6 | 0.45 | 0.9 | 12.3 | 9.01 | 50 | |
HR16016 | 1.6 mm × 16C | 1/1.6 | 1.6 | 0.45 | 0.9 | 13.7 | 9.01 | 50 | |
HR16020 | 1.6 mm × 20C | 1/1.6 | 1.6 | 0.45 | 0.9 | 15.2 | 9.01 | 50 | |
HR16024 | 1.6 mm × 24C | 1/1.6 | 1.6 | 0.45 | 0.9 | 17.0 | 9.01 | 50 | |
HR16024 | 1.6 mm × 30C | 1/1.6 | 1.6 | 0.45 | 0.95 | 18.2 | 9.01 | 50 | |
HR16002P | 1.6 mm × 2P | 1/1.6 | 1.6 | 0.45 | 0.9 | 10.2 | 9.01 | 50 | |
HR16003P | 1.6 mm × 3P | 1/1.6 | 1.6 | 0.45 | 0.9 | 11.3 | 9.01 | 50 | |
HR16004P | 1.6 mm × 4P | 1/1.6 | 1.6 | 0.45 | 0.9 | 12.6 | 9.01 | 50 | |
HR16005P | 1.6 mm × 5P | 1/1.6 | 1.6 | 0.45 | 0.9 | 13.8 | 9.01 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (2.0mm) | |||||||||
HR000200D | 2.0 mm × 1C | 1/2.0 | 2.0 | 0.45 | 0.9 | 4.7 | 5.77 | 50 | |
HR200D2 | 2.0 mm × 2C | 1/2.0 | 2.0 | 0.45 | 0.9 | 7.7 | 5.77 | 50 | |
HR200D3 | 2.0 mm × 3C | 1/2.0 | 2.0 | 0.45 | 0.9 | 8.2 | 5.77 | 50 | |
HR200D4 | 2.0 mm × 4C | 1/2.0 | 2.0 | 0.45 | 0.9 | 9.0 | 5.77 | 50 | |
HR200D5 | 2.0 mm × 5C | 1/2.0 | 2.0 | 0.45 | 0.9 | 9.8 | 5.77 | 50 | |
HR200D6 | 2.0 mm × 6C | 1/2.0 | 2.0 | 0.45 | 0.9 | 10.6 | 5.77 | 50 | |
HR200D8 | 2.0 mm × 8C | 1/2.0 | 2.0 | 0.45 | 0.9 | 11.5 | 5.77 | 50 | |
HR200D10 | 2.0 mm × 10C | 1/2.0 | 2.0 | 0.45 | 0.9 | 13.5 | 5.77 | 50 | |
HR200D12 | 2.0 mm × 12C | 1/2.0 | 2.0 | 0.45 | 0.9 | 14.0 | 5.77 | 50 | |
HR200D16 | 2.0 mm × 16C | 1/2.0 | 2.0 | 0.45 | 0.9 | 15.6 | 5.77 | 50 | |
HR200D20 | 2.0 mm × 20C | 1/2.0 | 2.0 | 0.45 | 0.9 | 17.4 | 5.77 | 50 | |
HR200D24 | 2.0 mm × 24C | 1/2.0 | 2.0 | 0.45 | 0.95 | 19.5 | 5.77 | 50 | |
HR200D30 | 2.0 mm × 30C | 1/2.0 | 2.0 | 0.45 | 1.05 | 21.0 | 5.77 | 50 | |
HR200D02P | 2.0 mm × 2P | 1/2.0 | 2.0 | 0.45 | 0.9 | 10.9 | 5.77 | 50 | |
HR200D03P | 2.0 mm × 3P | 1/2.0 | 2.0 | 0.45 | 0.9 | 12.1 | 5.77 | 50 | |
HR200D04P | 2.0 mm × 4P | 1/2.0 | 2.0 | 0.45 | 0.9 | 13.5 | 5.77 | 50 | |
HR200D05P | 2.0 mm × 5P | 1/2.0 | 2.0 | 0.45 | 0.9 | 14.8 | 5.77 | 50 |
Product Category | Product Code | Cross-sectional Area × Number of Cores mm² × C or P | Conductor | Insulation Thickness | Jacket Thickness mm | Finished Outer Diameter mm | Maximum Conductor Impedance in Ohms per Kilometer (Ω/km) | Minimum Insulation Resistance MΩ-km | |
---|---|---|---|---|---|---|---|---|---|
Construction No./mm | Outer Diameter mm | ||||||||
600V 380℃ Heat-resistant Fire Alarm Cable (1.25mm²) | |||||||||
HR000125 | 1.25 mm² × 1C | 7/0.45 | 1.35 | 0.45 | 0.9 | 4.1 | 16.8 | 50 | |
HR12502 | 1.25 mm² × 2C | 7/0.45 | 1.35 | 0.45 | 0.9 | 6.4 | 16.8 | 50 | |
HR12503 | 1.25 mm² × 3C | 7/0.45 | 1.35 | 0.45 | 0.9 | 6.8 | 16.8 | 50 | |
HR12504 | 1.25 mm² × 4C | 7/0.45 | 1.35 | 0.45 | 0.9 | 7.4 | 16.8 | 50 | |
HR12505 | 1.25 mm² × 5C | 7/0.45 | 1.35 | 0.45 | 0.9 | 8.0 | 16.8 | 50 | |
HR12506 | 1.25 mm² × 6C | 7/0.45 | 1.35 | 0.45 | 0.9 | 8.7 | 16.8 | 50 | |
HR12508 | 1.25 mm² × 8C | 7/0.45 | 1.35 | 0.45 | 0.9 | 9.4 | 16.8 | 50 | |
HR12510 | 1.25 mm² × 10C | 7/0.45 | 1.35 | 0.45 | 0.9 | 10.9 | 16.8 | 50 | |
HR12512 | 1.25 mm² × 12C | 7/0.45 | 1.35 | 0.45 | 0.9 | 11.3 | 16.8 | 50 | |
HR12516 | 1.25 mm² × 16C | 7/0.45 | 1.35 | 0.45 | 0.9 | 12.5 | 16.8 | 50 | |
HR12520 | 1.25 mm² × 20C | 7/0.45 | 1.35 | 0.45 | 0.9 | 13.9 | 16.8 | 50 | |
HR12524 | 1.25 mm² × 24C | 7/0.45 | 1.35 | 0.45 | 0.9 | 15.4 | 16.8 | 50 | |
HR12530 | 1.25 mm² × 30C | 7/0.45 | 1.35 | 0.45 | 0.9 | 16.4 | 16.8 | 50 | |
HR12502P | 1.25 mm² × 2P | 7/0.45 | 1.35 | 0.45 | 0.9 | 9.4 | 16.8 | 50 | |
HR12503P | 1.25 mm² × 3P | 7/0.45 | 1.35 | 0.45 | 0.9 | 10.4 | 16.8 | 50 | |
HR12504P | 1.25 mm² × 4P | 7/0.45 | 1.35 | 0.45 | 0.9 | 11.5 | 16.8 | 50 | |
HR12505P | 1.25 mm² × 5P | 7/0.45 | 1.35 | 0.45 | 0.9 | 12.6 | 16.8 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (2mm2) | |||||||||
HR000200 | 2 mm² × 1C | 7/0.6 | 1.8 | 0.45 | 0.9 | 4.5 | 9.43 | 50 | |
HR20002 | 2 mm² × 2C | 7/0.6 | 1.8 | 0.45 | 0.9 | 7.3 | 9.43 | 50 | |
HR20003 | 2 mm² × 3C | 7/0.6 | 1.8 | 0.45 | 0.9 | 7.8 | 9.43 | 50 | |
HR20004 | 2 mm² × 4C | 7/0.6 | 1.8 | 0.45 | 0.9 | 8.5 | 9.43 | 50 | |
HR20005 | 2 mm² × 5C | 7/0.6 | 1.8 | 0.45 | 0.9 | 9.2 | 9.43 | 50 | |
HR20006 | 2 mm² × 6C | 7/0.6 | 1.8 | 0.45 | 0.9 | 10.0 | 9.43 | 50 | |
HR20008 | 2 mm² × 8C | 7/0.6 | 1.8 | 0.45 | 0.9 | 10.9 | 9.43 | 50 | |
HR20010 | 2 mm² × 10C | 7/0.6 | 1.8 | 0.45 | 0.9 | 12.7 | 9.43 | 50 | |
HR20012 | 2 mm² × 12C | 7/0.6 | 1.8 | 0.45 | 0.9 | 13.2 | 9.43 | 50 | |
HR20016 | 2 mm² × 16C | 7/0.6 | 1.8 | 0.45 | 0.9 | 14.6 | 9.43 | 50 | |
HR20020 | 2 mm² × 20C | 7/0.6 | 1.8 | 0.45 | 0.9 | 16.3 | 9.43 | 50 | |
HR20024 | 2 mm² × 24C | 7/0.6 | 1.8 | 0.45 | 0.95 | 18.3 | 9.43 | 50 | |
HR20030 | 2 mm² × 30C | 7/0.6 | 1.8 | 0.45 | 0.95 | 19.5 | 9.43 | 50 | |
HR20002P | 2 mm² × 2P | 7/0.6 | 1.8 | 0.45 | 0.9 | 10.9 | 9.43 | 50 | |
HR20003P | 2 mm² × 3P | 7/0.6 | 1.8 | 0.45 | 0.9 | 12.1 | 9.43 | 50 | |
HR20004P | 2 mm² × 4P | 7/0.6 | 1.8 | 0.45 | 0.9 | 13.5 | 9.43 | 50 | |
HR20005P | 2 mm² × 5P | 7/0.6 | 1.8 | 0.45 | 0.9 | 14.8 | 9.43 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (3.5mm2) | |||||||||
HR000350 | 3.5 mm² × 1C | 7/0.8 | 2.4 | 0.45 | 0.9 | 5.1 | 5.2 | 50 | |
HR35002 | 3.5 mm² × 2C | 7/0.8 | 2.4 | 0.45 | 0.9 | 8.5 | 5.2 | 50 | |
HR35003 | 3.5 mm² × 3C | 7/0.8 | 2.4 | 0.45 | 0.9 | 9.1 | 5.2 | 50 | |
HR35004 | 3.5 mm² × 4C | 7/0.8 | 2.4 | 0.45 | 0.9 | 9.9 | 5.2 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (5.5mm2) | |||||||||
HR000550 | 5.5 mm² × 1C | 7/1.0 | 3.0 | 0.5 | 0.9 | 5.8 | 3.33 | 50 | |
HR55002 | 5.5 mm² × 2C | 7/1.0 | 3.0 | 0.5 | 0.9 | 9.9 | 3.33 | 50 | |
HR55003 | 5.5 mm² × 3C | 7/1.0 | 3.0 | 0.5 | 0.9 | 10.6 | 3.33 | 50 | |
HR55004 | 5.5 mm² × 4C | 7/1.0 | 3.0 | 0.5 | 0.9 | 11.6 | 3.33 | 50 | |
600V 380℃ Heat-resistant Fire Alarm Cable (8mm2) | |||||||||
HR000800 | 8 mm² × 1C | 7/1.2 | 3.6 | 0.5 | 0.9 | 6.4 | 2.31 | 50 | |
HR000802 | 8 mm² × 2C | 7/1.2 | 3.6 | 0.5 | 0.9 | 11.1 | 2.31 | 50 | |
HR000803 | 8 mm² × 3C | 7/1.2 | 3.6 | 0.5 | 0.9 | 11.9 | 2.31 | 50 | |
HR000804 | 8 mm² × 4C | 7/1.2 | 3.6 | 0.5 | 0.9 | 13.1 | 2.31 | 50 |